Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

11 - 4 Maintenance and Replacement

Issue 10 February 2008

Replacement Procedures, continued

!

Installing or Replacing a Rectifier, continued

Step

Action

3

Turn ac circuit breaker OFF.

4

Place rectifier power switch in STBY.

5

Verify that rectifier matches the ac input voltage of the
system.

DO NOT INSTALL 595B RECTIFIERS INTO

380/400/480Vac systems; they will will be damaged.

Continued on next page.