Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

13 - 6 Troubleshooting Millennium Systems

Issue 10 February 2008

CTRL

MAJ

Controller Fail

--

•BSH failure
•BSJ failure

•Option board

failure

•Display failure
•BIC failure

Check the BSJ board to see
if the green LED is
extinguished and the yellow
LED is lit. If so, perform
the following steps:
1. Press the SW201 reset

switch on the top of the
BSJ board. (This circuit
has an automatic restart,
which will try three
times to restart the
microprocessor.)

2. If the diagnostics did not

pass, or if the problem
recurs, remove all the
optional circuit board
cables, then press the
reset switch on the top of
the BSJ board again. If
all the diagnostics pass,
install optional circuit
board cables one at a
time, verifying operation
after each.

3. If the diagnostics did not

pass, replace the BSJ
board and verify the
failure is resolved. If so,
reinstall the optional
circuit boards and cables
one at a time.

4. If the problem is not

corrected, call technical
support.

Table 13-C: Controller Alarms (Continued)

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)