Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

Issue 10 February 2008

Rectifiers 4 - 3

Features

Output Voltage

Adjustment

This feature allows the rectifier output voltage to be set through the
controller.

Output Current

“Walk-in”

This feature controls the time (up to eight seconds) required for the
rectifier to reach normal operating conditions after it is turned on. This
feature minimizes the starting surge on the customer's power source.

Electronic Current

Limit

When the output current tends to increase above the current limit set
point (30% to 110% of rated output), the current limit circuit overrides
the voltage regulating signal and safely limits the output current of the
rectifier, thus preventing damage to itself, the battery, or the load.

Selective High

Voltage Shutdown

(SHVSD)

This feature allows the rectifier to respond and shut down at the output
high voltage threshold set through the Galaxy controller.

Backup High

Voltage Shutdown

(BHVSD)

This is a hardwired feature independent of the rectifier’s
microcontroller. This feature is always active and will operate whether
communicating with the controller or not and whether the rectifier's
microcontroller is active or failed.

Restart

Upon shutdown, the rectifier will attempt to restart. The rectifier will try
to restart three times before issuing a rectifier fail alarm to the controller.
The rectifier will also accept a restart command from the controller for
a remote restart.

Output Circuit

Breaker

The output circuit breaker located on the front panel protects the power
system from rectifier malfunction and may be used to disconnect the
rectifier from the system output bus.

Fan Alarm and

Control

The rectifier contains three cooling fans whose speed is based on
ambient temperature and output power level. The fan’s speed is lowered
during low-load and low-temperature conditions to minimize audible
noise and maximize fan life.