Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

13 - 10 Troubleshooting Millennium Systems

Issue 10 February 2008

RECT Alarm LED

Table 13-E: Rectifier Related Alarms

(See Figures 12-4 and 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)

RECT

MAJ

ID Not Configured None

None

Rectifier ID
number has not
been set.

Set rectifier ID using
procedure in Section
11, “Installing or
Replacing a Rectifier.”

RECT

MAJ

ID Conflict

None

None

Two or more
rectifiers have
the same ID
number.

See above.

RECT

MAJ

Multiple Rectifier
Fail

ALM

None

More than one
rectifier has an
ALM LED lit.

See alarms listed
below.

RECT

MAJ

High Voltage
Alarm

ALM

HO

•Lightning has

struck system.

•Internal rectifier

failure

1. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

2. If the problem is not

corrected, replace
the rectifier.

RECT

MIN

Rectifier Fail

ALM

HO

High output
voltage:
•Rectifier high

voltage
shutdown

•Internal rectifier

failure

1. Verify the

configurable HV
thresholds in the
controller.

2. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

3. If the problem is not

corrected, replace
the rectifier.