Troubleshooting tables, Organization, Table reference – GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual

Page 90: Rectifier display messages and leds, Organization 13-2 table reference

Advertising
background image

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

13 - 2 Troubleshooting Millennium Systems

Issue 10 February 2008

Troubleshooting Tables

Organization

The tables in this section are organized alphabetically by Alarm LED,
then grouped according to the status of the alarm: Critical (CRIT),
Major (MAJ), or Minor (MIN).

Table Reference

Use the reference below to locate the Alarm LED and corresponding
table.

Controller Alarm LED

Table

AC

13-A, AC Alarms

BATT

13-B, Battery Alarms

BD

13-F, Miscellaneous Alarms

CTRL

13-C, Controller Alarms

DIST

13-D, Distribution Alarms

RECT

13-E, Rectifier Related Alarms

RM

13-F, Miscellaneous Alarms

No LED*

13-F, Miscellaneous Alarms

*If an alarm condition exists, but no alarm LED is lit, refer to Table 13-F.

Rectifier Display

Messages and

LEDs

State

Display Message

LED

Illuminated

Normal

Current

ON

Output Limited

Current

LIM

Manual Standby

Blank

STBY

Remote Standby (Shutdown)

tr

STBY

Output Breaker Open

CB

ALM

Interlock Open

ILC

ALM

AC Fail

ACF

None

Phase Fail

PF

None

Over Temperature Shutdown

tA

ALM

Output Under Voltage Shutdown

LO

ALM

High Voltage Shutdown

HO

ALM

Internal Failure

LS, CS, IP5, IP6, IP7,

SEN, FSE, InF

ALM

Advertising