Troubleshooting Millennium Systems 13 - 3

Millennium

Controller Display

The Millennium display is illustrated below.

AC Alarm LED

Table 13-A: AC Alarms

(See Figure 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

AC

MIN

AC Fail

ACF on
rectifier
display

Rectifier is not
receiving ac power:
•AC input circuit

breaker has
operated.

•AC input voltage is

out of range.

•Internal rectifier

failure

1. Verify that ac circuit

breaker is closed; close
circuit breaker if
operated.

2. If the problem is not

corrected, replace the
rectifier.

AC

MIN

Engine Transfer
Timeout

Engine may
have alarm.

Remote engine or
connection to
engine has failed.

Call technical support.

AC

MIN

Phase Alarm

PF on
rectifier
display

Phase failure:
•Rectifier high

voltage shutdown

•External phase

imbalance or
failure

•Internal rectifier

failure

1. Toggle the ON/STBY

switch into the STBY
position and then back
into the ON position.

2. If the problem is not

corrected, replace the
rectifier.