Front panel display, Power switch, Status indicators – GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual

Page 32: Current display, Lamp test, Illustration, Illustration 4-2, Figure 4-1: rectifier front panel

Advertising
background image

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

4 - 2 Rectifiers

Issue 10 February 2008

Front Panel Display

Power Switch

This three-position switch has two active states:

It controls the on/standby state of the rectifier.

It is used to set the rectifier ID.

Status Indicators

In addition to the ON and STBY LEDs, four other LEDs on the
rectifier’s faceplate indicate the rectifier’s condition.

The ALM LED is red and lights when a thermal alarm occurs or a
rectifier fail condition occurs. This LED blinks when
communication with the plant controller is not active.

The LIM LED is yellow and lights when the unit is in current limit.

The FAN ALM LED is red and lights when the fan inside the
rectifier is not functioning properly.

The EQL LED is yellow and lights when the rectifier is in equalize
mode.

Current Display

This display indicates the current of the rectifier. Upon specific
no-power conditions, the 3-digit display will show informative
messages.

Lamp Test

To test the LEDs on the rectifier front panel, press the Lamp Test button
on the controller.

Illustration

Figure 4-1: Rectifier Front Panel

ON

ON

OFF

ID

CURRENT

STBY

ALM

LIM

FAN ALM

EQL

200A/48V