-DIPswitch settings for Vent length-

-Exhaust vent (Plastic vent)-

These models can be vented with a plastic vent which is made of PVC, CPVC, or polypropylene

(temperature rated up to 149 °F). In Canada, plastic venting must be certified to ULC S636 standards.

Item

Material

Canada

Exhaust pipe and

Fittings

Schedule 40 PVC

ULC S636 Certified

Materials Only

Schedule 40 CPVC

Polypropylene

Pipe Cement/Primer

PVC

CPVC

NOTE: Do NOT Use Cellular Foam Core Pipe

102 mm (4") venting

T-H3J-DV / 240H

T-H3S-DV / 340H

T-H3-DV / 540H

(Upper bank of DIPswitches)

Vent length

No. 6 : ON

No. 7 : OFF

No. 3 : ON

No. 4 : OFF

1.5 to 15.2 m

(5 to 50 ft)

(DEFAULT)

No. 6 : OFF

No. 7 : OFF

No. 3 : OFF

No. 4 : OFF

15.5 to 30.5 ft

(51 to 100 ft)

OFF

ON 1 2 3 4 5 6 7 8

OFF

ON 1 2 3 4 5 6 7 8

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

76 mm (3") venting

T-H3J-DV / 240H

T-H3S-DV / 340H

T-H3-DV / 540H

(Upper bank of DIPswitches)

Vent length

No. 6 : ON

No. 7 : OFF

No. 3 : ON

No. 4 : OFF

1.5 to 6.1 m

(5 to 20 ft)

(DEFAULT)

No. 6 : OFF

No. 7 : OFF

No. 3 : OFF

No. 4 : OFF

6.4 to 12.2 m

(21 to 40 ft)

No. 6 : ON

No. 7 : ON

No. 3 : ON

No. 4 : ON

12.5 to 21.3 m

(41 to 70 ft)

OFF

ON 1 2 3 4 5 6 7 8

OFF

ON 1 2 3 4 5 6 7 8

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8 9 10

OFF

ON 1 2 3 4 5 6 7 8

OFF

ON 1 2 3 4 5 6 7 8 9 10

Set DIPswitches shown in the table below depending on the vent length.

Installation

Installation Manual