-For sidewall terminations-

-For rooftop terminations-

For multiple sidewall exhaust terminations (e.g. multi-unit

systems), an exhaust termination must be at least 305mm

(1 ft.) away from another exhaust termination. An exhaust

termination must also be at least 610 mm (2 ft.) away

from an inside corner. (if the adjacent wall is less than 610

mm (2 ft.) of length, the minimum required distance away

from the inside corner will be equal to the length of that

adjacent wall.)

For multiple-unit, direct-vent sidewall terminations that

combine the intake and exhaust into a single penetration,

space each direct-vent termination at least 305 mm (1 ft.)

away from each other, no matter the orientation. A direct-

vent termination must also be at least 610 mm (2 ft.) away

from an inside corner. (if the adjacent wall is less than 610

mm (2 ft.) of length, the minimum required distance away

from the inside corner will be equal to the length of that

adjacent wall.)

For multiple-unit rooftop terminations (whether for standard or direct-vent installations) space all

exhaust and intake terminations in accordance with local codes. An exhaust termination must be spaced

from a wall or surface in accordance with local codes as well. In the absence of such a code, an exhaust

termination must be a horizontal distance of at least 610 mm (2 ft.) away from a wall or surface.

Exhaust and/or

direct-vent sidewall

terminations should

be at least 610 mm

(2 ft.) away from an

opposite surface/

wall. Do not place the

termination directly

in front of an opening

into a building

.

610 mm

(

2 ft.)

Exhaust

termination

Please follow all local and national codes in regards to proper termination

clearances. In the absence of such codes, the above clearances can be used as

guidelines. Local codes supersede these guidelines.

CAUTION

Installation

Exhaust

termination

Inside

corner

305 mm

(1 ft.)

610 mm

(2 ft.)

305 mm

(1 ft.)

Installation Manual

A: In accordance with local codes

Air intake

A

Exhaust termination

A

A

A

A

Air intake

610 mm

(2 ft)

Exhaust

termination

For direct-vent sidewall

terminations that use two

separate penetrations for

the intake and exhaust,

distance the intake and

exhaust terminations at

least 915 mm (3 ft.) away

from each other, no

matter the orientation.

915

mm

(3 ft.)

Air supply inlet

915 mm

(3 ft.)

915 mm

(3 ft.)

Exhaust

termination

Combined

intake and

exhaust

termination

Inside

corner

305 mm

(1 ft.)

610 mm

(2 ft.)

305 mm

(1 ft.)