-Stainless steel Vent Illustrations-

<How to install stainless steel venting>

• Regarding the clearances from the exhaust terminal to the air inlet or opening, refer to the

next few pages.

• Follow all vent system manufacturer’s instructions and all local codes.

• Do not common vent or connect any vent from other appliances to these models vent.

• Use 102 mm (4”) Category III/IV approved or Special BH, single or double wall stainless steel

vent pipe.

Horizontal Installation Diagram

Wall

Sidewall Vent

Terminator

Vertical Installation Diagram

Roof

Roof

Flashing

Fire stop

Rain Cap

102 mm (4") vent connection Diagram

Connect a 102 mm (4") stainless

steel vent straight pipe directly on the

exhaust and intake vent collar of the

water heater.

102 mm (4”) stainless

steel vent straight pipe

Exhaust vent collar

(Female)

Intake vent collar

(Female)

102 mm (4”)

stainless steel

vent straight

pipe

Diameter

Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length

102 mm (4 in.)

5

30.5 m (100 ft.)

*For each elbow added, deduct 1.5 m (5 ft.) from max. vent length.

No. of Elbows

Max. Vertical or Horizontal Vent Length

0

30.5 m (100 ft.)

1

29.0 m (95 ft.)

2

27.4 m (90 ft.)

5

22.9 m (75 ft.)

Excludes vent terminators, termination elbows, or rain caps.