Water connections, Measuring inlet gas pressure – John Wood Takagi - 240H-340H-540H User Manual

Page 22

Advertising
background image

22

Page

-Measuring inlet gas pressure-

The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions on

how to check the inlet gas pressure. THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL.

WATER CONNECTIONS

All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for

potable water systems.

1. A manual shutoff valve must be installed on the cold water inlet to the water heater between the main

water supply line and the water heater.

2. In addition, a manual shutoff valve is also recommended on the hot water outlet of the unit. If the

water heater is installed within, or subjected to, a closed loop water system, a thermal expansion tank

must be installed.

1. Turn off all electric power to the water heater if service is to be performed.

2. Turn the manual gas valve located on the outside of the unit clockwise to the

off position.

• Do not use this water heater if any part has been submersed under water.

Immediately call a licensed professional to inspect the water heater to replace

any damaged parts.

• Do not reverse the hot outlet and cold inlet connections to the water heater.

This will not properly activate the water heater.

CAUTION

Installation

Installation Manual

1. Shut off the manual gas valve on the gas supply line.

2. Remove the screw for the pressure port located on the gas

inlet of the water heater shown in the diagram on the right.

3. Connect the manometer to the pressure port.

4. Re-open the manual gas valve. Check to see that there are

no gas leaks. Open some of the fixtures that use the highest

flow rate to turn on the water heater.

5. Check the inlet gas pressure. When the water heater is on

maximum and minimum burn, the manometer should read

from 1.24 to 2.61 kPa (5.0” to 10.5” W.C.) for Natural gas,

from 1.99 to 3.48 kPa (8.0” to 14.0” W.C.) for Propane.

3. Before installing the water heater, flush

the water line to remove all debris, and

after installation is complete, purge

the air from the line. Failure to do so

may cause damage to the heater.

4. There is a wire mesh filter within

the cold inlet to trap debris from

entering your heater. This will need

to be cleaned periodically to maintain

optimum flow. (Refer to p. 41.)

Cold

inlet

Hot

outlet

Gas inlet

As Close as

Possible

Pressure Relief Valve

Pressure port

Advertising