Type 8696 positioner – Burkert Type 8696 User Manual

Page 17

Advertising
background image

17

Systemdescription

5.6.

Type 8696 positioner

The position measuring system records the current position (

POS) of the pneumatic actuator. The positioner com-

pares this actual position value with the set-point value (

CMD), which is definable as norm signal. In case of a control

deviation (Xd1), a pulse-width modulated voltage signal is sent to the control system as a manipulated variable. If
there is a positive control difference in single-acting actuators, the air inlet valve is controlled via output B1. If the
control difference is negative, the bleed valve is controlled via output E1. In this way the position of the actuator is
changed until control difference is 0. Z1 represents a disturbance variable.

Valve opening

Control valve

Control system
Solenoid valves

Position measuring system

Position
controller

Position
set-point
value

CMD

Xd1

B1

E1

P

K

Z1

POS

Position control circuit

+

-

Figure 5:

Signal flow plan of positioner

5.6.1.

Schematic representation of the position control Type 8696

4 ... 20 mA

2)

0 ... 20 mA

CHARACT

SPLTRNG

3)

DIR.CMD

CUTOFF

X.TIME

3)

X.CONTROL

DBND

POS

CMD

INP

POS
CMD

DIR.ACT

3)

X.LIMIT

3)

2)

Default setting

3)

can only be activated with communications software

Figure 6:

Schematic representation of the position control

english

Type 8696