46

Operationandfunction

12.1.3. CHARACT -

Select the transfer characteristic between input signal
(position set-point value) and stroke

Characteristic (customer-specific characteristic)

This function can be used to activate a transfer characteristic with respect to set-point value (set-point position)
and valve stroke for correction of the flow-rate or operating characteristic.

The transfer characteristic can be changed via the communications software only.

Factory setting: DIP switch 3 set to OFF (linear)

DIP Switches Position

Function

3

ON

Correction characteristic for adjustment of the operating characteristic
(linearization of the process characteristic

CHARACT)

20)

OFF

Linear characteristic

Table 21:

DIP switch 3

The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the correction characteristic (

CHARACT) which are modified via the communica-

tions software are only active if DIP switch 3 in the positioner is set to ON.

Characteristics which can be selected via the communications software:

Characteristic

Description

linear

Linear characteristic

1 : 25

Equal percentage characteristic 1 : 25

1 : 33

Equal percentage characteristic 1 : 33

1 : 50

Equal percentage characteristic 1 : 50

25 : 1

Inversely equal percentage characteristic 25 : 1

33 : 1

Inversely equal percentage characteristic 33 : 1

55 : 1

Inversely equal percentage characteristic 55 : 1

FREE

User-defined characteristic, freely programmable via nodes

Table 22:

Selection of characteristics

A detailed description of the characteristics can be found in the operating instructions for the communica-
tions software for positioners.

20)

The characteristic type can be changed via the communications software only.

english