Controlanddisplayelements

7.

CONTROL AND DISPLAY ELEMENTS

The following chapter describes the operating statuses as well as the control and display elements of the
positioner.

For further information on the operation of the positioner, refer to chapter “11. Start-up”.

7.1.

Operating status

AUTOMATIC (AUTO)

Normal controller mode is implemented and monitored in AUTOMATIC operating state.

→ LED1 flashes green.

MANUAL (MANU)

In MANUAL operating state the valve can be opened and closed manually via the keys.

→ LED1 flashes red / green alternately.

The DIP switch 4 can be used to switch between the two operating states AUTOMATIC and MANUAL.

7.2.

Control and display elements of the positioner

DIP Switches

Key 2

Key 1

LED 1

LED 2

Communications
interface

Figure 9:

Description of the control elements

The positioner features two keys, a 4-pole DIP switch and 2 2-coloured LEDs as a display element.

Screw off the transparent cap of the positioner to operate the keys and DIP switches.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!

• To observe protection class IP65 / IP67, screw the transparent cap in all the way.

Close the device (assembly tool: 674078

6)

).

6)

The assembly tool (674078) is available from your Bürkert sales office.