Operationandfunction

12.1.2. CUTOFF -

Sealing function for the positioner

This function causes the valve to be sealed outside the control range.

Control mode resumes at a hysteresis of 1%.

Factory setting: DIP switch 2 set to OFF (no sealing function)

DIP Switches Position

Function

2

ON

Sealing function active. The valve completely closes below 2 %

19)

and opens above 98 % of the set-point value (

CUTOFF)

OFF

No sealing function

Table 20:

DIP switch 2

The communications software can be used to change the limits for the position set-point value as a percentage.

The switching position of the DIP switches in the positioner has priority over the communications
software, i.e. settings of the sealing function (

CUTOFF) which are modified via the communications

software are only active if DIP switch 2 in the positioner is set to ON.

Valve stroke [%]

Adjustable from 75 – 100 %

Set-point
value [%]

Adjustable from 0 – 25 %

Figure 23:

CUTOFF graph