The positioner Type 8696 has different basic and additional functions which can be configured and parameterized
via the DIP switches or the communications software.

12.1. Basic functions

The following basic functions can be activated via the DIP switches (

CUTOFF and CHARACT) or changed

(

DIR.CMD).

Function

Description

DIP Switches OFF

ON

DIR.CMD

Effective direction between input
signal and set-point position

1

Rise

Fall

CUTOFF

Sealing function for positioner

2

Sealing function off

Sealing function on

CHARACT

Selection of the Transfer Charac-
teristic between Input Signal and
Stroke (Correction Characteristic)

3

Linear characteristic Correction

characteristic

Table 17:

Basic functions of DIP switches

Screw off the transparent cap of the positioner to operate the DIP switches.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!

• To observe protection class IP65 / IP67, screw the transparent cap in all the way.

Close the device (assembly tool: 674078

18)

).

The following basic function can be changed via the communications software only.

Function

Description

Factory setting

INPUT

Entry of the standard signal input
for the set-point value

4 ... 20 mA

Table 18:

Basic function of communications software

The

INPUT, CUTOFF and CHARACT functions can be parameterized via the communications software.

The operating instructions for the communications software describe in detail the individual functions, as
well as parameterization and configuration.

These instructions can be found on the Internet at

www.burkert.com

Documentation

Type 8696

and are also available on CD which can be ordered by quoting identification number 804625.