Pneumatic data, Type label – Burkert Type 8696 User Manual

Page 22

Advertising
background image

22

Technicaldata

6.5.

Pneumatic data

Control medium

neutral gases, air
Quality classes in accordance with DIN ISO 8573-1

Dust content

Class 5
max. particle size 40 µm,
max. particle density 10 mg/m³

Water content

Class 3
max. pressure dew point
- 20 °C or min. 10 °C below the lowest operating temperature

Oil content

Class 5
max. 25 mg/m³

Temperature range
of the compressed air

0 – + 50 °C

Pressure range

3 – 7 bar

Air output, pilot valve

7 I

N

/min (for aeration and deaeration)

(Q

Nn

value according to definition for pressure drop from 7 to 6 bar absolute)

Connections

23xx / 2103 (Element)

Plug-in hose connector Ø 6 mm / 1/4”

Threaded port G1/8

Model third-party device:

Socket connection G 1/8
with M5 connection for connecting to the third-party device

6.6.

Type label

Example:

8696 24 V DC

single act Pilot 0.6

Pmax 7 bar

Tamb 0°C - +55°C

S/N 001000

00177689

D-74653 Ingelfingen

W14UN

CE

Identification number

Supply voltage / Control

Max. pressure

Type

Control function - Pilot valve

Bar code

Serial number - CE mark

Max. ambient temperature

Figure 8:

Example of type label

english

Type 8696

Advertising