Controlanddisplayelements

7.4.

Function of the DIP switches

ON

DIP

1 2 3 4

To operate the DIP switches, unscrew the transparent cap.

NOTE!

Damage or malfunction due to penetration of dirt and humidity!

• To observe protection class IP65 / IP67, screw the transparent cap in all the way.

Close the device (assembly tool: 674078

10)

).

DIP Switches Position

Function

1

ON

Reversal of the effective direction of the set-point value (

DIR.CMD)

(set-point value 20 – 4 mA corresponds to position 0 – 100 %),
descending

OFF

Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position 0 – 100 %),
ascending

2

ON

Sealing function active. The valve completely closes below 2 %

11)

and

opens above 98 % of the set-point value (

CUTOFF)

OFF

No sealing function

3

ON

Correction characteristic for adjustment of the operating characteristic
(linearization of the process characteristic

CHARACT)

12)

OFF

Linear characteristic

4

ON

Operating status MANUAL (BY HAND)

OFF

Operating status AUTOMATIC (AUTO)

Table 9:

DIP Switches

Information about the communications software:

The switching position of the DIP switch has priority over the settings via the communications software!

If the values of the sealing function (

CUTOFF) or the correction characteristic (CHARACT) are changed

via the communications software, the corresponding function must be active (DIP switches set to ON).
The effective direction of the set-point value (

DIR.CMD) can be changed via the DIP switches only.

If the correction characteristic (

CHARACT) is not changed via the communications software, a linear char-

acteristic is saved when DIP switch 3 is set to ON.

A detailed description of the functions can be found in the chapter entitled “12.1. Basic functions” and in
the operating instructions for the communications software.

10)

The assembly tool (674078) is available from your Bürkert sales office.

11)

Factory setting, can be changed via communications software.

12)

The characteristic type can be changed via communications software