Burkert Type 8712 User Manual

Page 10

Advertising
background image

10

Descriptionofthesystem

Type 8006, 8702

5.3.2. mfc solenoid control valve

The solenoid valve used for an MFC is a direct-acting, normally closed
solenoid control valve.
The orifice size of the solenoid valve is determined by the required
nominal flow-rate Q

nom

, the pressure and temperature conditions in

the process and the density of the operating fluid.

If the device is operated within the specified pressure range,
the solenoid valve also takes over the sealing function
together with the control function. Limitation: in the case
of special hard seal materials, the sealing function cannot
be ensured. In this case an additional shut-off valve may
be required.

English

Advertising
This manual is related to the following products: