Electrical data – Burkert Type 8712 User Manual

Page 22

Advertising
background image

22

Technicaldata

Type 8006, 8702

6.7.

electrical data

Power supply

24 V DC ± 10%; residual ripple < 2% (5% for UL devices)

Power supply (not provided) for UL devices

Power supply limited to class 2

Power required (max. in Watt) depending on the type of the
device

8006

8702

8626

8712

12.5

5

36.5

14

MFC only:
Analogue input (configurable)

• 0/4 - 20 mA

Max. input impedance: 300

Ω, resolution: 5 µA

• 0 - 5/10 V

Min. input impedance: 20 k

Ω, resolution: 2.5 mV

Binary inputs (configurable)

3 binary inputs

Low active

Connect to DGND for activation

Analogue output (configurable)

• 0/4 - 20 mA

Max. load: 600

Ω, resolution: 20 µA

• 0 - 5/10 V

Max. current: 10 mA, resolution: 10 mV

On certain versions: Field bus communication
(alternative to "analogue input + outputs")

PROFIBUS DP V1, DeviceNet or CANopen

Relay outputs (configurable)

2 relay outputs
Potential-free changer 60 V, 1 A, 60 VA

LEDs (configurable)

4 LEDs
Status display for Power, Communication, Limit, Error

Electrical connections

M16 female fixed connector, 8-pin and Sub-HD, 15-pin

Additional connections for version with field bus

M12 male or female fixed connector, 5-pin, or Sub-D female fixed connector,
9-pin

English