Maintenance,Troubleshooting

Type 8626, 8712

problem

possible cause

recommended action

The limit (y) LED is
flashing

The device is in an operating state other than standard
control mode or the

Autotune function.

See section „8.3“.

The Error LED is on

Minor fault; for example the

Autotune function has failed. Repeat the Autotune

function or reset the device to acknowledge the fault.

The Error LED flashes

The residual ripple of the supply voltage is too high.

Use a power supply with a smooth output voltage at
the required power.

A major fault has occurred, for example: defective
sensor or internal voltage fault.

Return the device to the manufacturer to have the fault
repaired.

The sensor was operated above the permitted maximum
operating pressure.

Reduce the operating pressure.
Return the device to the manufacturer to have the fault
repaired.

No flow-rate available

The set-point value is below the limit for the zero point
shut-off.

Increase the set-point value to > 2% of the nominal
flow-rate.

The device is in an operating state other than standard
control mode.

Check the operating state; see also section „8.3“.

The lines have been sized too large or may not yet have
been completely deaerated.

Deaerate the lines.
Change the line diameter.