English – Burkert Type 8623 User Manual

Page 13

Advertising
background image

8623-2-Standard - 11

english

5.3

Connection configuration of flow controller type 8623-2

Fig.: Connections on flow controller type 8623-2

M12, 4 pole

supply voltage and

standard signal input

external set point

M8, 3-pole
Sensor 1

M8, 3-pole
Sensor 2
(with ratio control
only)

M12 (4-pole): Supply voltage and standard signal for setpoint

1 (brown)*

4 (black)

3 (blue)

2 (white)

Configuration

1

24 V DC supply voltage

2

Standard signal input, external setpoint

3

GND external set point

4

GND supply voltage

* wire colours when using standard cables with M12 plug (4-pole)

Configuration

1

24 V DC output

3

GND

4

Frequency input

M8 (frequency input, configuration of both plugs identical)

1 (brown)

4 (black)

3 (blue)*

* wire colours when using standard cables with M8 plug (3-pole)

Example of connection: flow rate sensor with coil (type 8020)

Type 8020 flow rate sensor
with coil

Type 8623-2 flow controller

Fig.: Connection of the flow rate sensor type 8020 with coil

4

3

M8 (3-pole)

1 (brown)

4 frequency input (black)

3 GND (blue)

Advertising