English – Burkert Type 8623 User Manual

Page 14

Advertising
background image

12 - 8623-2 Standard

english

Type 8020 flow rate sensor with
Hall-Sensor

Example of connection: flow rate sensor with Hall sensor
(type 8020)

Fig.: Connection of the flow rate sensor type 8020 with Hall sensor

Type 8623-2 flow controller

3

1

M8 (3-pole)

1 (brown)

4

3 (blue)

4 (black)

NOTE

For connection of flow rate sensor type 8020 with Hall sensor
to controller type 8623-2, a supply voltage is required (pin 1)!

Connection to 8020 (Hall sensor)

8020 (pin 1)

8623-2 (M8, pin 1 24 V DC output)

8020 (pin 2)

8623-2 (M8, pin 4 frequency input)

8020 (pin 3)

8623-2 (M8, pin 3 GND)

NOTE

For connection of flow rate sensor type 8020 with coil to
controller type 8623-2, no supply voltage is required!

Connection to 8020 (coil):

8020 (pin 2)

8623-2 (M8, pin 4 frequency input)

8020 (pin 3)

8623-2 (M8, pin 3 GND)

Advertising