English, 7 inv - inverted/non-inverted control – Burkert Type 8623 User Manual

Page 37

Advertising
background image

8623-2-Standard - 35

english

Example of an inverted control system

In the following system the actual value at the output of the unregulated pump is to
be controlled by changing the opening of the proportional valve in a return flow
loop. If the actual value is too high (x

d

<0), the correcting variable must be

increased (inverted control).

Example of an inverted control system

Î

Via this function you set the sense of action between the input signal and
the setpoint of the valve (factory setting: NO)

6.6.7

INV - inverted/non-inverted control

non-inverted control

y = K

p

(x

d

+ T

A

/T

N

x

d

)

inverted control

y = - K

p

(x

d

+ T

A

/T

N

x

d

)

non-inverted control (

NO):

Output signal of the PI controller
increasing positive control
difference x

d

= w-x.

inverted control (

YES):

Output signal Y of the PI controller
increasing negative control
difference x

d

= w-x.

working resistance

pump

sensor

proportional valve

Fig.: inverted/non-inverted control