8623-2-Standard - 27

english

Setting the setpoint: external setpoint

For external setpoint setting you state a scaling.
A range of flow rate corresponding to the standard signal (4 - 20 mA, 0 - 10 V) is
set here, i.e. the flow rate is entered at 4 mA or 0 V (lower limit) and at 20 mA or
10 V (upper limit).

Example:

lower limit (

EXLO)

0 l/min

4 mA

upper limit (

EXHI)

180 l/min

20 mA

Settings are possible between 0 and 655.2. If it is attempted to set a higher value,
the display will jump automatically to 0 and a value must be entered within the
range. The decimal point cannot be set at the first (left-hand) position. The unit
corresponds to the value set in the menu item UNIT.
(factory setting: EXLO=0.00; EXHI=180.00).

If the value for EXHI was selected lower than that for EXLO or
equal to it, the texts MODE and ERR 9 appear flashing
alternately on the text display.

In this case the newly set values are not stored!

increase digit

next digit

2x

set decimal point

standard signal
4 - 20 mA

standard signal 0 - 10 V

increase digit

next digit

2x

set decimal point

Fig.: Setting the setpoint: external setpoint