7

ERROR MESSAGES

Display

Cause

Correction

ERR0

Frequency 1 < 2 Hz or

sensor failure on
frequency input 1

Check flow rate sensor if applicable or

its connection to controller

ERR1

Frequency 2 < 2 Hz or

sensor failure on
frequency input 2

Check flow rate sensor if applicable or

its connection to controller

ERR2

Frequency 1 > 1000 Hz

Use a sensor matching the flow rate

ERR3

Frequency 2 > 1000 Hz

Use a sensor matching the flow rate

ERR4

Flow rate > 655

Use another unit (

UNIT

)

ERR5

Standard signal lies
outside range (4 - 20 mA,
0 - 10V)

Check standard signal

ERR6

Control not possible
since setpoint too great

Int. / ext setpoint mode:
Lower the setpoint or use another

sensor

Ratio Control mode:
Lower the ratio factor or use another

sensor

ERR7

Controller output to
proportional valve is >
95%

Increase the pressure in order to

reach the required setpoint with the
proportional valve selected

ERR8

Internal error

Send the device to the manufacturer

ERR9

Only in mode External
setpoint

EXLO

EXHI

Set the value correctly (see 6.6.4)

Actual value too great

(can no longer be

compensated) or in

manual mode, the valve

cannot be closed

Set the lower limit for valve drive

correctly (see 6.6.9. VALV)