38 - 8623-2 Standard

english

On using a direct acting proportional valve (Types 6022, 6023, 6024, 2832,
2834), set the greatest operating pressure expected in the application (the
start of opening is lowered with increasing admission pressure). With a pilot
controlled proportional valve (Type 6223), on the other hand, set the lowest
admission pressure to be expected in operation (in this case, the start of
opening is raised with increasing admission pressure).

Select the menu item VALV in the configuration mode. The actual value is
displayed.

If at the controller output obtaining no recognizable flow is present, first
increase the pulse-duty factor by pressing the

key until flow is detected.

Now lower the pulse-duty facotr by pressing the

key until the valve is

just closed, i. e. no flow is present.

Press the

key: the value for start of opening will be stored.

To determine the start of opening of the proportional valve in the current
application, the following steps are executed (on first operation of the device. This
is done immediately after switching on, while the coil is still cold):