English, 5 ampl - setting the amplification k – Burkert Type 8623 User Manual

Page 31

Advertising
background image

8623-2-Standard - 29

english

increase digit

next digit

2 s

set decimal point

6.6.5

AMPL - setting the amplification K

p

Î

Select the amplification factor K

P

in a range from 0.00 to 10.00

o

/

oo

/Hz

(factory setting: 1.00). If it is attempted to set a higher value, the display will
jump automatically to 0 and a value must be entered within the range.

Setting aid:

If excessive overshoot occurs at the value of K

P

set or the control

becomes unstable, you should decrease K

P

.

On the other hand, unsatisfactory control dynamics may be improved by
raising K

P

as long as the abovementioned instability does not occur.

Fig.: Setting the amplification K

P

Advertising