34 - 8623-2 Standard

english

From K

crit

and T

crit

, the controller parameters can then be calculated using the

following table.

Parameter setting according to Ziegler and Nichols:

The adjustment rules of Ziegler and Nichols have been determined for P members
with first order time increase and dead time.However, they apply only for
controllers with distrubance behaviour and not for those with command behaviour.

controller type

parameter setting

P

K

p

= 0,5 K

crit

-

PI

K

p

= 0,45 K

crit

T

N

= 0,85 T

crit