Technicaldata

Current consumption

• Version with transistor

output

• Version with 1 single

output, relay or current

• version with 1 relay and

1 current outputs

• 50 mA max.

• 70 mA max.

• 90 mA max.

Protection against polarity
reversal

yes

Transistor output

NPN and/or PNP, 700 mA max.,
operation and thresholds can be
parametered
NPN output: 0,2-36 V DC,
PNP output: supply voltage

Relay output

250 V AC, 3 A max, operation and
thresholds can be parametered

Protection against short
circuits

yes, for the transistor output

Table 2:

Electrical data specific to the UL threshold detector

Characteristics of the
power source (not
supplied)

• Limited power source (in accordance

with § 9.3 of the UL 61010-1
standard)

• or class 2 type power source

(according to the 1310/1585 and
60950-1 standards)

Drain current

30-50 mA

Table 3:

Electrical data for flowmeters

4-20 mA output

• Accuracy
• Wiring
• Loop resistance


• Galvanically insulated
• 4 mA adjustment
• 20 mA adjustment
• Response time (10% up to

90%)

• ±0.5%
• 4 wires
• 1300W at 36 V DC, 1000W at

30 V DC, 700 W at 24 V DC,
450 W at 18 V DC, 200W at
12 V DC

• yes
• between 3 and 5 mA
• between 18.5 and 21.5 mA
• 3 s with filter 2 (default setting)

6.3.4. Data of the cables and wires

version

type of connector

Detector with
NPN transistor
output

EN 175301-803 female connector (type 2508,
supplied)

Detector with
PNP transistor
output

EN 175301-803 female connector (type 2508,
supplied)