9.6.1. Adjusting the 4-20 mA output

0......9

ENTER

ENTER

ENTER

*

0......9

*

0......9

ENTER

ERR 11 ?

ENTER

MA

To the function "END" of the Test menu

3.95

OFFS

20.50

span

YES

MA

NO

MA

no

yes

* to move the decimal point, simultane-

ously press keys

0......9

and

• When the function "OFFS" is displayed, the device gives a 4-mA current.

Measure the current given on the 4-20 mA output using a multimeter.

Enter this value in the function

OFFS

. The permitted offset range is 3 to 5 mA.

Press ENTER to confirm.

• When the function "SPAN" is displayed, the device gives a 20-mA current.

Measure the current given on the 4-20 mA output using a multimeter.

Enter this value in the function

SPAN

. The permitted span range is 18,5 to 21,5 mA.

• Confirm or do not confirm the values entered by choosing "

YES MA

" or "

NO MA

". When the message "ERR11" is displayed, at least one of the

values entered is outside the permitted range: see chap. 10.3.