Wiring the version with both relay and current, Outputs (5-pin m12 fixed connector) – Burkert Type 8072 User Manual

Page 25

Advertising
background image

23

Installationandwiring

+ -

i

(*)

+ -

4

3

1

2

5

i

i

Power supply

12-36 V DC

4-20mA input
(at external
instrument)

brown

blue

shield

black

white

grey

Fig. 24: Wiring of the current output, in sinking mode, of a

version with a single 5-pin M12 fixed connector

+ -

i

(*)

+ -

4

3

1

2

5

i

i

shield

grey

Power supply

12-36 V DC

4-20mA input
(at external
instrument)

brown

blue

black

white

Fig. 25: Wiring of the current output, in sourcing mode, of a

version with a single 5-pin M12 fixed connector

(*) Functional earth

7.3.6. Wiring the version with both relay

and current outputs (5-pin m12 fixed
connector)

Warning

shock hazard due to the voltage at the relay terminals, which
is higher than 48v.
• Before powering the device, always check that the connectors

are correctly plugged-in and tightened.

the device is not tight when the en 175301-803 fixed
connector is not wired:

Unscrew the nut [1] (see Fig. 10) on the 2508 female
connector supplied with the device.

Insert the plug with order code 444509, supplied with
the device, into the cable gland.

Screw the nut back.

Plug the sealed 2508 connector onto the
EN 175301-803 fixed connector.

1

2

3

1

2

3

1: Common

2: Relay, normally closed (NC)

3: Relay, normally open (NO)

4: not connected

Fig. 26: Pin assignment on the EN 175301-803 fixed connector

English