Setting the flow rate range associated to the, 20 ma output, Choosing the filter of the flow rate – Burkert Type 8072 User Manual

Page 38: Ma 0.200, Filt 2

Advertising
background image

36

Adjustmentandfunctions

9.5.4. setting the flow rate range

associated to the 4-20 mA output

The 4-20 mA output provides an electrical current, the value of
which reflects the flow rate measured by the device.
• The signal may be inverted, i.e. the flow rate value associated to the

20-mA current is lower than the one associated to the 4-mA current.

• The current output gives a 22-mA current when the device shows

an operating error.

4

20

20

180

mA

l/min

Fig. 38: Example of relation between the measuring range and

the current output

ENTER

0......9

*

0......9

*

ENTER

ENTER

MA

0.200

4ma

1.000

20ma

To function "FILT"

* to move the
decimal point,
simultaneously
press keys

0......9

and

Enter the flow rate values, in the unit that has been chosen in the
UNIT parameter, related to the 4-20-mA current range.

9.5.5. choosing the filter of the flow rate

To function "BRGR"

ENTER

0......9

ENTER

FILT

2

FILT

The "Filter" function is used to attenuate the display and 4-20 mA
output, if any, fluctuations when the flow rate varies in the process.
Ten attenuation levels, from 0 (means no attenuation) to 9 (maximum
attenuation of the fluctuations) are available.
Table 4:

Response times of the current output and the display
depending on the filter chosen

Filter N°

Response time (10% up to 90%)

0

300 ms

1

1,5 s

2

3 s

3 (by default)

5 s

4

7 s

5

11 s

6

20 s