Adjustmentandfunctions

Window operation
The change of state is done whenever one of the thresholds is
detected.

Not inverted

Contact

Flow
rate

ON

OFF

OLO OHI

Inverted

Contact

Flow
rate

ON

OFF

OLO OHI

Fig. 36: Window operation of the transistor output

The time delay (DEL) is valid for both output thresholds. switching
is only done if one of the thresholds (OHI - OLO) is exceeded for a
duration longer than this time delay.

2 s

OHI

OLO

2 s

2 s

DEL = 0 s

DEL = 2 s

DEL = 0 s

DEL = 2 s

ON

OFF
ON

OFF
ON

OFF
ON

OFF
ON

OFF
ON

OFF
ON
OFF
ON
OFF

OUT

t

hysteresis operation

Not inverted

Not inverted

Inverted

Inverted

Inverted

Inverted

Window operation

Flow rate

Not inverted

Not inverted

Fig. 37: Examples for the behaviour of the transistor or relay

output of a 8032 / 8072, depending on the flow rate and
the operation chosen.

English