Configuring the selectors, Flow sensor selector, Source/sink selector – Burkert Type 8025 User Manual

Page 30: English, Fig. 23: position of the source / sink selector

Advertising
background image

30

Wiring

Type 8025 / 8035

Wire the transistor output using one of the wiring plans of "Fig. 21".

Wiring of the pulse output in npn mode

300 mA

+

-

12-36 V DC

(*)

+

-

1

3

2

L+

L-

P+

P-

8025:
NPN

P+

P-

+

- 5-36 V DC

Power supply

PLC

Wiring of the pulse output in pnp mode

+

-

300 mA

+

-

12-36 V DC

(*)

1

3

2

L+

L-

P+

P-

8025:
PNP

P+

P-

+

- 5-36 V DC

Power supply

PLC

(*) If direct earthing is not possible, insert a 100 nF / 50 V condensator between the negative terminal of the voltage supply and the earth.

Fig. 21: Wiring of the pulse output in NPN or PNP mode, of a compact version with male fixed connector

8.3.

configuring the selectors

Only move the selectors when the power supply is off.

Before wiring the device, configure the selectors on the electronic board: see chap. "8.3.1" to "8.3.3".

8.3.1. floW sensor selector

The FLOW SENSOR selector makes it possible to configure the type of flow sensor: coil or Hall.

For the version with male fixed connector, the selector is factory-set depending on the output signal of the flow
sensor mounted on the device.

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

FLOW SENSOR

COIL

NPN

PE

Fig. 22: Position of the FLOW SENSOR connector on the electronic board
Tab. 4: Positioning of the FLOW SENSOR selector depending on the output signal of the flow sensor

Version of the flowmeter

output signal of the remote sensor

position of the floW sensor selector

All

Pulse, NPN (hall)

NPN

All

Sinus (coil)

COIL

8.3.2. source/sinK selector

The Source/Sink selector makes it possible to set the 4-20 mA current output of the versions with relays, in sourcing or in
sinking mode. Set the selector depending on the type of wiring.

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

SOURCE SINK

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

SOURCE SINK

Without

Relays

PE

Fig. 23: Position of the Source / Sink selector

English

Advertising