Adjusting the span of the current output, Checking the outputs behaviour – Burkert Type 8025 User Manual

Page 57

Advertising
background image

57

operatingandcommissioning

Type 8025 / 8035

9.7.2. Adjusting the spAn of the current output

This parameter makes it possible to adjust the 20 mA current value transmitted on the 4-20 mA output.

Connect a multimeter into the measurement loop.

The device generates a 20 mA current.

Measure the current given on the 4-20 mA output using a
multimeter.

Enter the value displayed by the multimeter. The permitted span
range is 15 to 21,50 mA.

Confirm.

SPAN

FREqUENC

ENTER

ENTER

SP= 19.90

SP= 20.00

0......9

Fig. 67: Adjustment of the SPAN

If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press

ENTER

to save the

settings and go back to the Process level.

9.7.3. reading the rotational frequency of the paddle wheel

FREqUENC

195.3 hz

FLOw

ENTER

ENTER

Fig. 68: Diagram of the "FREQUENC." parameter of the Test menu

If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press

ENTER

to save the

settings and go back to the Process level.

9.7.4. checking the outputs behaviour

This parameter makes it possible to simulate a flow rate in order to check that the outputs are behaving as expected by the
configuration made.

Enter a flow rate value, in the unit chosen in the "UNIT" parameter.

Confirm by pressing the

ENTER

key. the display returns on the

"FLOW" parameter.

Check that the outputs are behaving as expected.

To test another value, press

ENTER

.

To exit the checking, press

or

0......9

.

FLOw

ENTER

46.25 L/S

00.00 L/S

0......9

Fig. 69: Diagram of the "FLOW" parameter of the Test menu

If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press

ENTER

to save the

settings and go back to the Process level.