Entering the k factor of the fitting used – Burkert Type 8025 User Manual

Page 52

Advertising
background image

52

operatingandcommissioning

Type 8025 / 8035

9.6.3. entering the K factor of the fitting used

The device determines the flow rate in the pipe using the fitting K factor.
The K factor of the fitting used can be entered here. The device may also determine the K factor using a teach-in procedure:
see "Fig. 58".

The K factor of the fitting used is in the operating instructions of the fitting.
The operating instructions of the Bürkert fittings can be found on the CD delivered with the device or on the internet
at:

www.burkert.com

.

tEACh NO

K=0000.00

K=0117.60

CURRENt

ENTER

0......9

The display shows the K factor of the fitting,
last entered or determined using a Teach-In
procedure.

Edit the parameter.

Enter the K factor (value between 0,0001
and 9999,9) of the fitting used.

Confirm the displayed value.

K-FACtOR

ENTER

ENTER

Fig. 57: Entering the K factor of the fitting used

K-FACtOR

tEACh NO

0000.0 L

K=0079.30

CURRENt

0......9

tEACh y

FiLL END

0100.00 L

Charge the pipe to fill the tank.

When the tank is full, confirm "FILL
END"

The device calculates the

K factor of the fitting and

displays it.

ENTER

ENTER

ENTER

ENTER

The teach-in is done depending on a known volume.

Prepare a tank with a known volume.

Stop the fluid circulation.

Confirm "TEACH Y.": "FILL END." is displayed.

ENTER

0......9

Do not enter a volume value equal
to 0,0 because the K Factor cal-
culated would be equal to 0,0 and
the device would not operate.

Enter the volume (value > 0,0 and

≤ 9999,9) of fluid that passed in the
circuit.

Confirm.

Fig. 58: Teach-in procedure depending on a volume

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to

save the settings and go back to the Process level.