Operating and commissioning, Safety instructions, Operating levels of the device – Burkert Type 8025 User Manual

Page 46

Advertising
background image

46

operatingandcommissioning

Type 8025 / 8035

9.

operATinG AnD commissioninG

9.1.

safety instructions

Warning

risk of injury due to nonconforming operating.
Non-conforming operating could lead to injuries and damage the device and its surroundings.
• The operators in charge of operating must have read and understood the contents of this manual.
• In particular, observe the safety recommendations and intended use.
• The device/installation must only be operated by suitably trained staff.

Warning

Danger due to non-conforming commissioning.
Non-conforming commissioning could lead to injuries and damage the device and its surroundings.
• Before commissioning, make sure that the staff in charge have read and fully understood the contents of the manual.
• In particular, observe the safety recommendations and intended use.
• The device / the installation must only be commissioned by suitably trained staff.
• Before commissioning, set the K Factor of the fitting used. See chap. "9.6.3".

9.2.

operating levels of the device

The device has two operating levels: the Process level and the Configuration level.
The Process level makes it possible:
• to read the flow rate measured by the device, the value of the current transmitted on the 4-20 mA analogue output, the

values of both the daily and main totalizers;

• to reset the daily totalizer;
• to access the Configuration level.
The Configuration level has two menus (Parameters, Test) and makes it possible:
• to set the device parameters;
• to test some device settings.
Tab. 6: Default settings of the device

function

Default value

LANGUAGE

English

UNIT of the flow rate

L/min, 1 decimal

UNIT of the totalizers

L

Number of decimal positions

1

4 mA current output

0.000

20 mA current output

100.0

K FACTOR

51.20

FILTER

5

Value of a pulse (PU)

00.05

Unit of the pulse output

L

Relay 1-

40.0

Relay 1+

50.0

Relay 1 inverted

no

Relay 2-

80.0

Relay 2+

90.0

Relay 2 inverted

no

English

Advertising