Quick installation – Burkert Type 8041 User Manual
Page 16
14
Quickinstallation
7.
QuicK insTAllATion
Contact your Bürkert
agent
→
Unpack the device.
Order code
correct?
→
Loosen 4 screws and remove
cover.
yes
No
→
Select the frequency of the main
supply with switch 1, see chap.
→
Select the filter with switches 2
and 3, see chap. 9.5.
→
Select the current output type,
see chap. 8.3.1.
The following formulae are used to calculate the K
1
and K
2
factors
needed to convert the current or frequency into a flow rate:
Full scale
K factor K
1
K factor K
2
10 m/s
K
1
= 100
K
fitting
K
2
= 20
3*K
fitting
5 m/s
K
1
= 200
K
fitting
K
2
= 40
3*K
fitting
2 m/s
K
1
= 500
K
fitting
K
2
= 100
3*K
fitting
where K
fitting
= K factor of the S020 fitting used
Example:
If the full scale of the device is set to 5 m/s, the value of the current
output will be:
I = 40 Q + 4
3*K
fitting
with I in mA, K
fitting
in pulse/litre and Q in l/s.
English
Type 8041