Maintenanceandtroubleshooting

problem

bargraph
state

red leD state

Green leD
state

current or
frequency
output
state

meaning / cause

recommended action

The device
does not
respond

OFF

Flashes once
briefly every 2 s

Flashes once
every second

22 mA and
256 Hz

Measuring range
exceeded by more than
20%

Clear the error by briefly pressing the
push-button.

Consult the graphs (see chap.
8.2.1).

The device
does not
respond

OFF

Flashes twice
briefly every 2 s

Flashes once
every second

22 mA and
0 Hz

The flow zero point cali-
bration failed.

Clear the error by briefly pressing the
push-button.

Check upstream/downstream dis-
tances (see chap. 8.2.1).

Restart the calibration (see chap.
9.7).

If the error persists, contact your
Bürkert retailer.

The device
does not
respond

OFF

Flashes 3 times
briefly every 2 s

Flashes once
every second

22 mA and
0 Hz

The device is out of
service

Contact your Bürkert retailer.

The device
does not
respond

OFF

Flashes 4 times
briefly every 2 s

Flashes once
every second

22 mA and
0 Hz

The full scale calibration
failed because the fluid
velocity < 2 m/s

Clear the error by briefly pressing the
push-button.

Check the fluid velocity.

Restart the calibration of the full
scale (see chap. 9.8).