Calibrating the full scale – Burkert Type 8041 User Manual

Page 38

Advertising
background image

36

Adjustmentandcommissioning

9.8.

calibrating the full scale

The Fig. 30 and the Fig. 31 show the relation between the measured
fluid velocity and the value of the frequency or current provided by
the outputs.

256

Hz

0

m/s

0.1

240

Full scale error

Calibrated full scale

Full scale + 20%

Fig. 30: Relation between the measured fluid velocity and the value

of the frequency output

22

mA

0

m/s

0.1

20

4

Calibrated full scale

Full scale + 20%

Full scale error

Fig. 31: Relation between the measured fluid velocity and the value

of the current output

If no predefined measuring range is applicable to your process, the
device can be calibrated with the actual max. flow velocity of the
application.
The low bound of the measuring range is 0 m/s.

Position the switches 4 and 5 to ON (see

Fig. 26, chap. 9.2).

Install the device on the pipe as described in chap.

8.

Allow the fluid to circulate in the pipe at maximum velocity.

Calibrate the full scale, see

Fig. 32 and Fig. 33.

English

Type 8041