2 alarm level classification – IAI America ACON-SE User Manual

Page 102

Advertising
background image

92

6. T

roubleshooting

6.2 Alarm Level Classification

Alarms are classified into the following two levels in accordance with the symptoms they represent:

Alarm level

ALM lamp

Failure status

register

What happens when

alarm generates

How to reset

Operation
cancellation

/LW UHG 

$/0/LV³´

The actuator
decelerates to a stop
and then the servo
turns OFF.

- Reset the alarm by the

PC/teaching pendant.

- Input the reset signal from the

PLC.

Cold start

/LW UHG 

$/0+LV³´

The actuator
decelerates to a stop
and then the servo
turns OFF.

- Reset software by the

PC/teaching pendant.

- Reconnect the power.

Caution: Reset each alarm after identifying and removing the cause. If the cause of the alarm

cannot be removed or when the alarm cannot be reset after removing the cause, please
contact IAI.
If the same error occurs again after resetting the alarm, it means that the cause of the
alarm has not been removed.