2 alarm level classification – IAI America ACON-SE User Manual
Page 102
92
6. T
roubleshooting
6.2 Alarm Level Classification
Alarms are classified into the following two levels in accordance with the symptoms they represent:
Alarm level
ALM lamp
Failure status
register
What happens when
alarm generates
How to reset
Operation
cancellation
/LWUHG
$/0/LV³´
The actuator
decelerates to a stop
and then the servo
turns OFF.
- Reset the alarm by the
PC/teaching pendant.
- Input the reset signal from the
PLC.
Cold start
/LWUHG
$/0+LV³´
The actuator
decelerates to a stop
and then the servo
turns OFF.
- Reset software by the
PC/teaching pendant.
- Reconnect the power.
Caution: Reset each alarm after identifying and removing the cause. If the cause of the alarm
cannot be removed or when the alarm cannot be reset after removing the cause, please
contact IAI.
If the same error occurs again after resetting the alarm, it means that the cause of the
alarm has not been removed.