IAI America SSEL User Manual

Page 271

Advertising
background image

249

Part 2 Programs

z ECMD20 (Get parameter value)

Command, declaration

Extension condition

(LD, A, O, AB, OB)

Input condition

(I/O, flag)

Command,
declaration

Operand 1

Operand 2

Output

(Output, flag)

Optional Optional ECMD 20

Variable

number

CC

[Function] Store the value of the specified parameter in variable 99, using the data stored in the three

consecutive variables starting from the one corresponding to the variable number specified in
operand 2.
If variable No. n is set in operand 2, the data in variable No. n will indicate the parameter type,
data in variable No. n+1 will indicate the device number (or axis number), and data in variable
No. n+2 will indicate the parameter number, respectively. The ranges of parameter type,
device number (or axis number) and parameter number are specified below. If an out-of-
range value is specified, “C44, SEL data error” will generate.

I/O

Common

to all axes

Axis-

specific

Driver Encoder

I/O

device Other

Parameter

type

0

1

2

3

4

5

7

Device number/axis number

0

0

1 ~ 2

1 ~ 2

1 ~ 2

0 ~ 7

0

Parameter number

1 ~ 300

1 ~ 120

1 ~ 200

1 ~ 97

1 ~ 30

1 ~ 82

1 ~ 100

Specify an integer variable in operand 2 (integer variables 98, 99, 298, 299, 1098, 1099, 1298 and
1299 cannot be specified, because three consecutive integer variables cannot be allocated if any
of these integer variables is specified). If a variable of non-integer type is specified, “C3C, Variable
number error” will generate.

(Note)

If an invalid axis number is specified in operand 2, “C44, SEL data error” will generate.

[Example 1]

LET

10

2

Variable No. 10 = Parameter type (Axis-specific)

LET

11

2

Variable No. 11 = Axis number (Axis 2)

LET

12

42

Variable No. 12 = Parameter number (No. 42)

ECMD

20

10

Extended command 20 (Use variable Nos. 10 through 12)

Store the value of axis-specific parameter No. 42 (axis 2),
“Encoder resolution,” in variable 99.

[Example 2]

LET

1250

0

Variable No. 1250 = Parameter type (I/O)

LET

1251

0

Variable No. 1251 = Device number (0, in the case of I/O
parameter)

LET

1252

30

Variable No. 1252 = Parameter number (No. 30)

ECMD

20

1250

Extended command 20 (Use variable Nos. 1250 through
1252)

Store the value of I/O parameter No. 30, “Input function
selection 000,” in variable 99.