Wiring accessories to the expansion board, Additional features – LiftMaster LA500 Residential / Light Commercial Swing Gate Operator User Manual
Page 37
35
Com
Single Button Control Station
A
SBC
3-Button Control Station
B
C
Com
Open
Close
Stop
AUX Relay 2 N.C.
Com
AUX Relay 2 N.O.
AUX Relay 1 N.C.
Com
AUX Relay 1 N.O.
Exit Loop
Interrupt Loop
Shadow Loop
D
E
F
G
H
I
ADDITIONAL FEATURES
A
Open Input (& common)
(3-Button Control Station, 4 terminals total)
Open command - opens a closed gate.
Soft open (maintained switch does not override external safeties and does not reset alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate.
B
Close Input (& common)
(3-Button Control Station, 4 terminals total)
Close command - closes an open gate.
Soft close (maintained switch does not override external safeties and does not reset alarm condition)
C
Stop Input (& common)
(3-PB station, 4 terminals total)
Stop command - stops a moving gate.
Hard stop (maintained switch overrides Open and Close commands and resets alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Overrides an Open or Close command.
D
Single Button Control, SBC (2 terminals)
Gate command sequence - Open, Stop, Close, Stop, ...
Soft Open ,Soft Close, Soft Stop (maintained switch does not override external safeties and does not reset alarm condition)
E
Exit Loop Input (2 terminals)
Loop wire connection for plug-in loop detector when loop is inside secured area near gate.
Open command - opens a closed gate.
Soft open (maintained switch does not override external safeties and does not reset alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate.
F
Shadow Loop Input (2 terminals)
Loop wire connection for plug-in loop detector when loop is positioned under the gate.
- Holds open gate at open limit
- Disregarded during gate motion
- Pauses Timer-to-Close at Open Limit
G
Interrupt Loop Input (2 terminals)
Loop wire connection for plug-in loop detector when loop is along the side of the gate.
- Holds open gate at open limit
- Stops and reverses a closing gate
- Pauses Timer-to-Close at Open Limit
H
AUX Relay #1
Normally - open and normally - closed relay contacts to control external devices,
Function of relay contact activation determined by AUX Relay #1 option switch settings. (For connection of Class 2, low voltage
(42 Vdc [34 Vac] max 5 Amps, power sources only)
I
AUX Relay #2
Normally-open and normally-closed relay contacts to control external devices,
Function of relay contact activation determined by AUX Relay #2 option switch settings. (For connection of Class 2, low voltage
(42 Vdc [34 Vac] max 5 Amps, power sources only)
Aux Relay
N.C.
COM
N.O.
Class 2 Power Source
(42 Vdc [34 Vac],
5 A max)
+
—
Warning Light
AUX RELAY WIRING EXAMPLE
WIRING ACCESSORIES TO THE EXPANSION BOARD
WIRING ACCESSORIES TO THE EXPANSION BOARD
Refer to the chart below and the corresponding image for a description of the expansion board inputs.