Specifications, Ac power, Battery (lead acid only) – System Sensor PDRP-1002 User Manual

Page 10: Initiating device circuits, Notification appliance and releasing circuits, Alarm and trouble relays, Four-wire smoke detector power, Non-resettable power, Rms regulated power

Advertising
background image

1 The PDRP-1002/PDRP-1002E

AC Power

10

The PDRP-1002 PN 51135:A 03/11/99

Specifications

AC Power

For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps
For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH. (Batteries larger
than 12 AH require NOTIFIER #BB-17 or other UL
listed external battery cabinet.)

Initiating Device Circuits

Power-limited circuitry
Operation: Class A (Style D)/Class B (Style B)
Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including end-of-line resistor)

Notification Appliance and Releasing Circuits

Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps

Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)

Alarm and Trouble Relays

Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC
(resistive). All relays must be connected to a power limited power supply.

Four-wire Smoke Detector Power

Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p

Non-resettable Power

Total DC current available from this output is up to 200 mA (subtracted from 4-wire
smoke power).
Maximum ripple voltage: 1.0 V p/p

RMS Regulated Power

Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p

Note: For device compatibility, refer to Device Compatibility Chart.

AC Circuit
Breaker

Ac

c

tb

rk

r.

c

d

r