1 The PDRP-1002/PDRP-1002E

Transmitter Module (4XTM - NOTIFIER)

8

The PDRP-1002 PN 51135:A 03/11/99

Optional Boards

The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of
the three option modules may be installed.

Transmitter Module (4XTM - NOTIFIER)

The Transmitter Module provides a supervised output for
local energy municipal box transmitter (for NFPA 72
Auxiliary Fire Alarm System) and alarm and trouble
reverse polarity circuits (for NFPA 72 Remote Station Fire
Alarm System). Also included is a DISABLE switch and
disable trouble LED.

As a jumper option, the alarm reverse polarity circuit will
open on trouble if no alarm exists.

LED Interface Module (4XLM - NOTIFIER)

The LED Interface Module supports the RZA-4X Remote
Annunciator module. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver
Module mounts to the main board, occupying one of the
two option connectors.

Zone Relay Module (4XZM - NOTIFIER)

The Zone Relay module provides Form-C contacts for the
following:

As a jumper option, the first four relays described below can
be made silenceable.

DIP 1=OFF
Either Zone

DIP 1=ON
Cross Zone

If Supervisory (DIP 2=ON)

Either Zone

Cross Zone

Alarm Detected

First Alarm

Alarm Detected First Alarm

Alarm Detected

Second Alarm Alarm Detected Second Alarm

Release 1

Release 1

Release

Release

Release 2

Release 2

Not Used