Transmitter Module - 4XTM (NOTIFIER)

3 Installation Procedure

The PDRP-1002 PN 51135:A 03/11/99

23

Transmitter Module - 4XTM (NOTIFIER)

Polarities shown in activated positions. The wiring of this module must follow the
requirements as specified in the “General” section, “UL Power Limited Wiring
Requirements.

Push the disconnect switch down to prevent unwanted activation of the Municipal Box
and Remote Station Outputs during testing of the control panel. The Disconnect LED
will remain illuminated while the Municipal Box is disconnected. The System Trouble
LED will indicate disconnected and/or Open Circuit conditions on the Municipal box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble,
if no alarm exists
.

Note: Remote Alarm, Remote Trouble, and Municipal Box wiring can leave the building.

-

-

-

+

+

+

}
}

}

1

2

3

4

5

6

7

TBL Jumper

Disconnect LED

Disconnect Switch

Remote Alarm

Remote Trouble

No Connection

Municipal Box*

* Dummy load terminals
6 and 7 (4.7K, 1/4 W
resistor) if Municipal
Box is not connected.

Power Limited Circuit

Non-Power Limited Circui

4X

T

B

a.

cd

r