Zone relay module - 4xzm (notifier) – System Sensor PDRP-1002 User Manual

Page 24

Advertising
background image

3 Installation Procedure

Zone Relay Module - 4XZM (NOTIFIER)

24

The PDRP-1002 PN 51135:A 03/11/99

Zone Relay Module - 4XZM (NOTIFIER)

Non-power limited and power limited wiring must have a minimum distance of 0.25 in.
(6.35 mm) wire to wire. If this module is used to drive non-power limited and power
limited circuits, please follow the instructions below.

1)

Skip a set of dry contacts to maintain the 0.25 in (6.35 mm) required space

between power limited and non-power limited circuits. The wiring of this module must
follow the requirements as specified in the “General” section, “UL Power Limited
Wiring Requirements
.”

OR

2)

If this module is needed to drive power limited and non-power limited relays that

are next to each other, refer to the figure below showing a typical connection.

Relay #1 through #4 will activate with Output #1 through #4
and remain latched unless jumper “LATCH” is cut.

1 NO

2 NC

3 C
4 NO

5 NC
6 C
7 NO

8 NC

9 C

10 NO
11 NC

12 C
13 NO
14 NC

15 C

16 NO
17 NC

18 C

Relay #1

Relay #2

Relay #3

Relay #4

Alarm

Trouble

Cut jumper for non-latching (silenceable) relay operation.

Use Disable switch to disconnect the relays.

4X

Z

M

A

.cdr

Note: Refer to the Protected Premises Unit label, located on the door of the control panel, to
indicate if any dry contacts are to be used as non-power limited dry contacts.

4X

Z

M

p

tl

.cdr

Relay #1

Relay #2

Relay #3

Relay #4

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

Power Limited Circuit

Power Limited Circuit

No Connection

Non-power Limited Circuit

Non-power Limited Circuit