Remote annunciator, Optional meters, Transmitter module (4xtm - notifier) – System Sensor PDRP-1002 User Manual

Page 9: Led interface module (4xlm - notifier), Zone relay module (4xzm - notifier), Remote annunciator (rza-4x - notifier), Voltage, current meters (4xmm - notifier), Maximum voltage/current, each output: 27.6v/8ma

Advertising
background image

Transmitter Module (4XTM - NOTIFIER)

1 The PDRP-1002/PDRP-1002E

The PDRP-1002 PN 51135:A 03/11/99

9

Transmitter Module (4XTM - NOTIFIER)

For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA
Trip current: 0.35 amps. (Subtracted from Notification Appliance power)
Coil Voltage: 3.65 VDC
Coil resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building

For Remote Station service (NFPA 72 Remote Station Fire Alarm
System):

Maximum load for each circuit: 10mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building

LED Interface Module (4XLM - NOTIFIER)

Maximum voltage/current, each output: 27.6V/8mA

Note: Outputs are power limited

Zone Relay Module (4XZM - NOTIFIER)

Dry Form-C contacts rated: 2.0 amps @ 30VDC (resistive), 0.5 amps @ 30 VAC
(resistive)

Remote Annunciator

Remote Annunciator (RZA-4X - NOTIFIER)

The Remote Annunciator mounts on a standard single-
gang box, and provides LED indication of the same
functions as the zone relay module. For example with
DIP 1=ON and DIP 2=OFF:

One Zone in Alarm (red)

Two Zones in Alarm (red)

Releasing Circuit 1 (red)

Releasing Circuit 2 (red)

System Trouble (yellow)

A Local Trouble Sounder and Silence Switch are also
provided. All LED wiring is supervised for open
conditions. Any open condition will cause the System
Trouble LED to illuminate.

Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).

Optional Meters

Voltage, Current Meters (4XMM - NOTIFIER)

The Meter Module provides a voltmeter to measure the
voltage across the batteries and an ammeter to measure
the charging current to the batteries. The meters are
provided as an assembly that mounts to the lower left-
hand corner of the cabinet.