Output 4 Supervisory/Releasing Service

3 Installation Procedure

The PDRP-1002 PN 51135:A 03/11/99

27

Output 4 Supervisory/Releasing Service

Set the function of Output 4 via SW1 DIP switch 2.

Timer

Select the desired Timer setting and set SW1 DIP switches 3 and 4 per the appropriate
column.

Abort Function

Select the desired abort functions and set SW1 DIP switches 5 and 6 per the appropriate
column.

Note: ABORT timer will not operate when timer is set for “NO DELAY”.

Switch 2

OFF

ON

Output 4 will function as a
solenoid releasing circuit. This
circuit will be a non-power
limited circuit in this mode.

Output 4 will function as a supervisory input
circuit. A short condition on this circuit will
illuminate the Supervisory LED and sound
the supervisory tone on the piezo. An open
condition generates a circuit trouble
condition. This circuit will function as a
power limited circuit in this mode.

No Delay*

10 Seconds

20 Seconds

30 Seconds

Switch 3

OFF

OFF

ON

ON

Switch 4

OFF

ON

OFF

ON

*Abort switch is inoperative when no delay is selected.

Switch 1

OFF

OFF

ON

ON

Switch 2

OFF

ON

OFF

ON

Standard UL-type
delay
timer which
continues to count down
upon ABORT, and stops
and holds at 10 seconds
until release of the
ABORT switch. Upon
release of the ABORT
switch, the timer
resumes the countdown
at 10 seconds.

IRI-type delay
timer
which
functions the same as
the UL-type timer
with the exception
that the ABORT will
function only if
pressed and held
before 2nd zone goes
into alarm.

NYC-type delay
timer.
Pressing
ABORT, once an
alarm exists, changes
timer value to the
time selected via DIP
Switches 3 and 4
plus 90 seconds.
The timer will not
start as long as the
ABORT switch is
held. SYSTEM
RESET restores
timer to original
times selected via
DIP Switches 3 and
4. Successive
ABORTS will add
90 seconds to
selected timer value.

Local Jurisdiction
delay timer.
Once
the timer has started,
pressing ABORT
restores timer to its
full time as set on
DIP Switches 3 and
4. The timer will
not start as long as
ABORT is held.
Release of the
ABORT switch
continues the
countdown, whereas
pressing ABORT
again will restore
the timer to its full
value.

These modes are the only ones that
comply with UL Standard 864